Bovema UK - Ventilation Systems Specialists

Quick Links

Go straight to the page you need
Certification & Other Info

VDS VDS
CE Manuals

CE Manual (Dutch) CE Manual (Dutch)
English version available upon request
Map
Bovema UK
The Business Centre
Cardiff House
Cardiff Road
Barry CF63 2AW
phone:
08450 840555
fax:
08450 840556
email:

NKV-RD

Technical Information

Impact Safety Test

No information available yet.

Thermal Insulation

Thickness of operable flaps in mm
1.5 6 10 16 16k 20 25k
Single skin aluminium 5.6
Polycarbonate 3.1 2.3 2.0
Double skin aluminium panel,
thermally insulated
1.9 1.9 1.8
K-value in W/m²k

Sound Reduction

Thickness of blade material in mm
1.5 6 10 16 16k 20 25k
Single skin aluminium
Polycarbonate 17 21 21 21 22
Double skin aluminium panel,
thermally insulated
Rw-value in dB
according ISO 717

Transparency

    Main Clear Opal
Georgian wired, toughened
or laminated glass 6mm:
6 mm 90%    
Polycarbonate 10 mm   80% 48%
Polycarbonate 16 mm   76% 48%
Polycarbonate 20 mm   64% 37%
Polycarbonate 25 mm 44% 24%

Air Capacity

Snow Load

According BS7346: Part 1: 1990 standards the uninsulated NKV-RD can carry a snow load up to 125 N/m². The insulated types can carry a snow load of 300 N/m². These values are applicable with an opening of 30° or less.

Temperature Resistance

Standard minimum -20°C/ maximum +100°C
Cylinder minimum -20°C/ maximum +60°C
Motor minimum -5°C/ maximum +70°C

Rain Defence

The NKV-RD is waterproof in closed position, according the standards of BS7346: part 1: 1990 Clause 5.3.

Wind Resistance

The NKV-RD meets the standards of BS7346: part 1: 1990 and opens successfully with a side wind of 18 m/s (Clause 5.6).
Image Coming Soon
Bovema manufacture and install Smoke Ventilation Systems, Natural Ventilation Systems, Powered Ventilation Systems and Bespoke Specialist Applications.
All rights reserved
Bovema UK Ltd © 2007
Website Search Engine Optimisation by Designer Websites Ltd