Technical Information

Impact Safety Test

No information available yet.

Thermal Insulation

Thickness of operable flaps in mm
  1.5 6 10 16 16k 20 24 25k 30 60 60+ spc
Single skin aluminium 5.6                      
Glass   5.1                    
Polycarbonate 3.1 2.3 2 1.8 1.7
Insulated glass standard           3 2.9   2.8      
Insulated glass type HR           2 1.8 1.7 1.6      
Double skin aluminium       1.9 1.9 1.8 1.6 1.5 1.3 0.45 0.4 0.4
K-values in W/m²k                        

Sound Reduction

Thickness of blade material in mm
  1.5 6 10 16 16k 20 24 25k 30 60 60+ spc
Single skin aluminium 6                      
Glass                        
Polycarbonate 17 21 21 21 22
Insulated glass standard           32 35 36 37      
Insulated glass type HR           32 35 36 37      
Double skin aluminium           22 24 25 28   38 42
Rw-value in dB
according ISO 717

Transparency

    Main Clear Opal
Glass 6 mm 90%    
Insulated Glass 20/24/25/30mm 90%    
Polycarbonate 10 mm   80% 48%
Polycarbonate 16 mm   76% 48%
Polycarbonate 20 mm   64% 37%
Polycarbonate 25 mm   44% 24%
         

Air Capacity

Snow Load

According BS7346: Part 1: 1990 standards, the NKVD-PS can carry a snow load up to 50 kg/m².

Temperature Resistance

Standard minimum -20°C and maximum +70°C. The NKVD-PS is fire tested successful at 300˚C.

Rain Defence

The NKVD-PS is waterproof in closed position, according the standards of BS7346: part 1: 1990 Clause 5.3.

Wind Resistance

The NKVD-PS meets the standards of BS7346: part 1: 1990 and opens successfully with a side wind of 18 m/s (Clause 5.6).
NKVD-PS
+ Click image to enlarge
NKVD-PS
+ Click image to enlarge
NKVD-PS
+ Click image to enlarge
NKVD-PS
+ Click image to enlarge
NKVD-PS
+ Click image to enlarge
NKVD-PS
+ Click image to enlarge
Bovema manufacture and install Smoke Ventilation Systems, Natural Ventilation Systems, Powered Ventilation Systems and Bespoke Specialist Applications.
All rights reserved
Bovema UK Ltd © 2007
Website Search Engine Optimisation by Designer Websites Ltd