TMS-DG

Specification

Impact Safety Test

The apparatuses of the type TMS have been tested and found test good on Impact Safety Test means the 1200 joule. See report "1200 Joule CEBTP".

Sound Reduction

The TMS with insulated flanges and alutherm louvres are acoustically measured according NEN 20.240-1965, ISO 140/11-1978 and DIN 52.210-1984.

Middle frequency hertsband in Hz: Rw
Sound reduction in dB: 18 dB
   

Insulation Information

1.5 + 1.0 mm single skin aluminium: 5.7 W/m²K
20 mm double skin aluminium: 5.7 W/m²K
20 mm insulated double skin aluminium: 1.4 W/m²K
10 mm alusandwich: 1.9 W/m²K
10 mm polycarbonate 2RS translucent/opal: 3.0 W/m²K
6 mm single, laminated, toughened or wired glass: 5.6 W/m²K
   

Transparency

Single, laminated, toughened or wired glass 6mm: 90%
Polycarbonate 10 mm 2RS translucent/opal: 80% (translucent)/
48% (opal)
   

Air Capacity (CV-value)

Roof transit
Height
  Alu1
≤ 20
90°
Alu1
> 20
90°
Alu2
≤ 20
70°
Alu2
> 20
70°
Profile
louvres
90°
400 mm LB 0.70 0.65 0.65 0.60 .0.65
LBi 0.70 0.65 0.65 0.60 .0.65
HB 0.65 0.60 0.60 0.55 0.60
HBi 0.70 0.65 0.65 0.60 .0.65
300 mm LB 0.70 0.65 0.65 0.55 0.65
LBi 0.70 0.65 0.65 0.55 0.65
HB 0.60 0.55 0.55 0.55 0.60
HBi 0.70 0.65 0.65 0.55 .0.65
200 mm LB 0.65 0.60 0.60 0.55 0.65
LBi 0.65 0.60 0.60 0.55 0.65
HB 0.60 0.55 0.55 0.50 0.60
HBi 0.65 0.60 0.60 0.55 0.65
100 mm LB 0.65 0.60 0.60 0.55 0.65
LBi 0.65 0.60 0.60 0.55 0.65
HB 0.60 0.55 0.55 0.50 0.55
HBi 0.65 0.60 0.60 0.55 0.65
0 mm LB 0.65 0.60 0.60 0.55 0.65
LBi 0.65 0.60 0.60 0.55 0.65
HB 0.60 0.55 0.55 0.50 0.55
HBi 0.65 0.60 0.60 0.55 0.60
             
LB = Low base, non insulated
HB = High base, non insulated
LBi = Low base, insulated
HBi = High base, insulated

Temperature Resistance

Standard minimum -20°C/ maximum +100°C
Cylinder minimum -20°C/ maximum +60°C
Motor minimum -5°C/ maximum +70°C

Rain Defence

The TMS-D is waterproof in closed position, according the standards of BS7346: part 1: 1990 Clause 5.3.

Wind Resistance

According EN12101-2 standards, the TMS has a wind resistance of SL 1500 N/m².
TMS-DG
+ Click image to enlarge
TMS-DG
+ Click image to enlarge
TMS-DG
+ Click image to enlarge
TMS-DG
+ Click image to enlarge
TMS-DG
+ Click image to enlarge
TMS-DG
+ Click image to enlarge
TMS-DG
+ Click image to enlarge
TMS-DG
+ Click image to enlarge
TMS-DG
+ Click image to enlarge
TMS-DG
+ Click image to enlarge
Bovema manufacture and install Smoke Ventilation Systems, Natural Ventilation Systems, Powered Ventilation Systems and Bespoke Specialist Applications.
All rights reserved
Bovema UK Ltd © 2007
Website Search Engine Optimisation by Designer Websites Ltd