TSL-V

Specification

Sizes

Height 500 to 3600 mm
Depth 350 mm
Width (N x 160) + 200, minimum 840 mm
Space between attenuators 200 mm
Attenuator thickness 200 mm

Weights

  Height
Width 1000 1500 2000 2500 3000 3500
1000 49 65 80 96 112 127
2000 83 109 136 162 189 215
3000 116 154 191 228 266 303
4000 150 198 246 295 343 391
5000 184 243 302 361 420 479
6000 217 287 357 427 497 567
7000 251 332 413 493 574 655
8000 285 376 468 560 651 743
 

Air Capacity (AW-value)

  Width
  ≤1500 >1500
Opened without sound attenuator 0.50 0.45
Half open without sound attenuator 0.40 0.37

Materials

  • Corrosion resistant aluminium;
  • Extruded aluminium sections AlMgSi 0.5;
  • Fixings in stainless steel;
  • Weather-resistant EPDM seals.

Motor Information

The TSL-V does not use an motor.

Controls

  • Cable control

Installation

Please take notice of the following instructions:
  • Only use Stainless steel fixings;
  • Drill the holes in the flange with a minimum measure the width of the bolt and a maximum measure of HOH 500 mm;
  • be assembled on the fireset.
  • Assembly and maintenance should only be performed in daylight or artificial light.